New exploitation confirmation, not a new discovery
On 25 November 2026, CISA added CVE-2023-25915, CVE-2023-25914 and CVE-2025-41450 affecting Danfoss AK-SM 800A to KEV. This controller family is used in areas including refrigeration management. The new event is confirmed exploitation, not disclosure of all three flaws on the same day.
For retailers, warehouses and cold-chain logistics, controller access can affect operational continuity and configuration confidentiality. The reviewed entries do not establish physical equipment damage, product loss or a shared campaign. These CVEs are not automatically identified as the cause of every earlier refrigeration incident described by ENISA.
Check each CVE's version scope and preconditions
CVE-2023-25915 allows an authenticated attacker with network access to execute commands. CVE-2023-25914 also requires authentication and exposes server files through the XML interface. DIVD CNA records cover AK-SM800A before 3.3; the historical 3.3 fix addresses these issues, not every later vulnerability affecting the controller.
For CVE-2025-41450, the Danfoss CNA record identifies AK-SM 8xxA before 4.2 and an authentication flaw. KEV describes generation of a report exposing information including internal IP addresses, usernames and store names. That is distinct from command execution in CVE-2023-25915. Version 3.3 must not be treated as sufficient remediation for the entire set.
Our recommendations:
Work with the process owner and service provider to establish models, versions, locations and remote-access paths. Remove unnecessary direct controller exposure, restrict service accounts and separate OT from ordinary IT segments. Account for alarm dependencies and emergency access so a security change does not cut off plant support.
Confirm the currently supported firmware for the exact model. The 3.3 and 4.2 thresholds help identify historical fixes but do not replace current guidance. Prepare a configuration backup, agreed window, on-site contact and manual recovery procedure. Agree testing and any version rollback with the vendor; returning to vulnerable firmware is not a safe final state.
Do not perform aggressive scans or exploitation attempts against operating controllers. Start with inventory and an agreed version check. Preserve login and parameter-change history, review vendor accounts and investigate unknown communications. Signs of tampering require process-safe isolation and incident response involving OT personnel.
Post-change checks and source limitations
After updating, verify the version, restored configuration, alarms, monitoring and refrigeration process. Retain completion evidence and recovery-test results. An application with no visible errors does not establish absence of earlier access.
Danfoss advisories were not readable during verification because the site returned 403. Version scope was checked in public CNA records and DIVD material, not a newly read vendor matrix. KEV records forensicTriage: Yes and a 28 November deadline for both 2023 CVEs; CVE-2025-41450 records No and 9 December 2026. All three have ransomware: Unknown. US federal deadlines do not automatically impose legal deadlines on Polish businesses.
Sources
- DIVD-2023-00025: AK-SM800A research and remediationSource updated: 2024-04-25. Checked: 2026-11-26.
- CVE Program: CVE-2023-25915Checked: 2026-11-26.
- CVE Program: CVE-2023-25914Checked: 2026-11-26.
- CVE Program: CVE-2025-41450Checked: 2026-11-26.
- CISA KEV: official catalog 2026.11.25Source updated: 2026-11-25. Checked: 2026-11-26.
Checked full KEV, three CVE Program records and DIVD-2023-00025 on 26 November. Danfoss returned 403; no new advisory revision date is assigned. Version scope comes from DIVD and Danfoss CNA records. No automatic link to earlier ENISA refrigeration incidents is asserted. Public analysis, not original LS Core research.